Technical FAQs

Ask a Question

ATV212HD15N4 mounting info needed on spacing mounting vertically.

What is the minimum mounting space between the top and bottom of the ATV212H series drives?

Product Line:
Altivar ATV212 drive


Wants to mount the ATV212 Drives vertically.

The ATV212 installation manual has the Drive mounting generalities. 
In this case the min mounting clearance between the top and bottom of the drive is 2 inches top and 2 inches from the bottom. 

The ATV212 Drives side to side mounting is also 2 inches if the top cover is still in place on the drive.  If you remove the top cove you can mount side by side no minimum distance. 

Was this helpful?
What can we do to improve the information ?