Browse FAQs

What would cause the ATV61 and ATV71 drive to show auto tune in progress and not complete the auto tune process?

Published date: 03 September 2019

Issue:
What would cause the ATV61 and ATV71 drive to show auto tune in progress or pending and not complete the auto tune process?

Product Line:
Altivar 61 and 71

Environment:
All 

Cause:
Auto tune process will not complete (stalled, pending) since the is in PRA or non ready mode. 

Resolution:
The drive's status needs to be RDY before the Auto Tune can complete.  If the Drive is in a PRA or non RDY mode the tune status will come back as not complete.
Check the factory installed jumper between the PRA and the +24vdc power supply.  If this jumper is loose it will cause the drive not to complete the Auto tune process.

Was this helpful?

What can we do to improve the information ?

Can't find what you are looking for?

Reach out to our customer care team to receive information on technical support, assistance for complaints and more.