How to change the template on an ATV630 and ATV930 so that the 0 %speed is at low speed instead of 0 hz?

Issue:
How to change the template on an ATV630 so that the 0 %speed is at low speed instead of 0 hz? 
 
Product Line:
ATV630
 
Environment:
Pedestal and deadband
 
Cause:
n/a
 
Resolution:
Parameter BSP can have a setting of Standard, Pedestal, Deadband or Deadband 0 % : 
When you see the Keypad: BSP can be standard , Deadband, pedestal or pedestal at 0%: 
The term is inverted on keypad : Deadband should be Pedestal and pededstal /pedestal at 0% should Deadband/Deadband at 0%. 
Same problem with SoMove: 
The solution to set Pedestal like on ATV71, is to set Deadband on ATV6XX/ATV9xx. 