The M221 PLC does not go in RUN mode

Issue:
While online with a M221 PLC it is impossible to put it into Run mode.

Product Line:
PLC

Environment:
M221

Resolution:
If PLC is only powered with the USB connection, you can not put the PLC into Run mode. You need to supply the PLC with power on the appropriate terminals to be able to have it in RUN mode.

 