Issue:
Differentiating Plug-On / Non-Plug-On Neutral QO™ Breakers & Panels

Product line:
QO branch circuit breakers

Environment:
Installation 

Resolution:
LC = Load Center
PoN = Plug-On Neutral 

The standard, QO, QO-CAFI (Non-PoN), QO-DF (Non-PoN), QO-GFI (Non-PoN), QO-EPD/EPE (Non-PoN), QO-SWN, QO-HID, QO-K and QO-HM branch circuit breakers can be installed in all QO load centers.

The QOT tandem breakers can ONLY be installed in the QO load centers that are designed to accept the QOT Tandem breakers. (See FA130326 to determine if a QO Load Center accepts tandems)

The QO, PoN Arc Fault, Ground Fault and Dual Function Breakers can ONLY be installed in the QO, PoN series Load Centers.

Below is a graphic visual of the Standard QO and QOT branch breakers being installed on the interior of a Standard QO load center. This information is available in the below attached instruction bulletin.

QO Breaker Installation


NOTE: PLEASE MAKE SURE FOLLOW ALL THE SAFETY INFORMATION PROVIDED AND NEVER WORK ON ENERGIZED EQUIPMENT.

 