How can I get 5% line impedance for the ATV630 Process Drives?

Issue:
Customer is looking for equivalent to 5% line reactor on the Altivar Process drive.

Product line:
ATV630, ATV600, Altivar Process

Environment:
all

Cause:
Needs an equivalent to 5% line impedance, on the Altivar Process drive.

Resolution:
To achieve a 5% line impedance we would add a 3% line reactor ahead of the drive.  

We do not offer Line reactors for the Altivar Process Drives.  Please contact a manufacturer such as MTE Corp for selection.