Where can I find basic programming information for ATV drive?

Issue:
Where can I find basic programming information for ATV drive?

Product Line:
ATV930

Environment:
All

Cause:
Basic programming.

Resolution:

Under drive menu:

t CC= 2/3 wire control
CG= Macro con fig
bF r= Standard motor frequency 60 hz
nPr= Rated motor power= HP size of the motor
U nS= Rated motor voltage =  motor voltage
nCr= Rated motor current= motor amps
FrS= Rated motor Frequency= 60 hz
NS= Rated motor speed= motor r pms
fF r= Max Frequency= Hz
Itch= Motor Thermal Current= Amps
ACC= Ramp up time acceleration
DEC= Ramp down time deceleration
LP= Low speed setting
HP=High speed setting

Command Menu:
Far= AI 1 for remote pot control
      = AI 2 for analog input 4-20 mA control
      = (See the ATV programming manual for other options)
CHIC= Not separate or Separate (depends on where start/stop and speed controls are coming from)
RC= Reference switching.

Refer to the programming manual for in depth explanation and menu structure.

 