Environment:
All serial numbers for Altivar Process Drive
Cause:
N/A
Resolution:
Altivar 6xx Series:
This Function is not available
Altivar 9xx Series:
To program the drive with a Permanent Magnetic Synchronous Motor
Set Motor Control Type - [Complete settings] [Motor parameters] [Motor Control Type] Ctt
[Sync. mot.] Syn - Open-loop synchronous motors: Motor control type specific for permanent magnet synchronous motors.
[Sync.CL] FSy - Open-loop synchronous motor: For motors with Encoders or motors with sinusoidal electromotive force (EMF) only
[SYN_U VC] SYnU - Open-loop synchronous motor: This motor control type is used for variable torque applications.
[Rel. Mot.] - Synchronous Reluctant Motor: Opened loop synchronous motor without permanent magnet. This motor control type is used for variable torque applications.
Setup Motor data parameters - [Complete settings] [Motor parameters] [Motor data]
[Sync Nominal I] nCrS - Sync motor nominal current.
[Nom SyncMotor Speed] nSPS - Nominal synchronous motor speed.