Technical FAQs

Ask a Question

With a SCADAPack 575 What Does the Message "This isn't a valid PLC Address, or PLC is busy, or media is off" mean?

When using a SCADAPack 575 and attempting to connect the logic debugger if the message "This isn't a valid PLC Address, or PLC is busy, or media is off" is displayed it can mean that the Logic Debugger service is not enabled in the rPAC.

To remedy this:
  1. Return to RemoteConnect
  2. Open the offline configuration
  3. In the "SCADAPack x70 Logic" section enable the "Logic Debugger Service"
  4. Download the configuration again.
Was this helpful?
What can we do to improve the information ?