ATV320 drive how do you set up your reference 1 channel so that local knob is the speed reference and the digital input is the start command. 

Issue:
ATV320 drive how do you set up your reference 1 channel so that local knob is the speed reference and the digital input is the start command. 

Product Line:
All 

Environment:
All 

Cause:
Programming setting up the local knob for speed control and using the digital input for start stop. 

Resolution:
CONF > FULL > CTL-
FR1 change from AI3 to A1U1

CHCF set to SEP (You must press and hold the enter button for 3 seconds to change this parameter.)
CD1 is terminal . 
After the programming is complete, press ESC until you are back at RDY.   In order to control the speed, you must press Enter twice.   This will place you in the REFerence menu and allow you to adjust the motor speed with the jog dial on the front of the drive.   If power is ever cycled to the drive, you will need to press Enter twice again to re-enter this menu.
 