Technical FAQs

Ask a Question

Why is it important to keep SPD wires as short as possible?

Product Line: 
Surge Protective Devices (SPDs)

Resolution:
To obtain the maximum system performance, locate the device as close to the circuit being addressed as possible to minimize the interconnecting wiring length. For every foot of wire length, approximately 160 Volts (6 kV / 3 kA, 8/20 microsecond) is added to the suppressed voltage. The Voltage Protection Rating (VPR) is located on the device nameplate and is measured six inches from the enclosure sidewall, according to UL® 1449 test standards.
Was this helpful?
What can we do to improve the information ?