Video: Can the ATV320 be programmed using an external 24Vdc source?

Issue:
Can the ATV320 be programmed using an external 24Vdc source?

Product line:
Altivar 320

Environment:
External 24v
 
Cause:
Need power the ATV320 with external 24Vdc so that it can be programmed

Resolution:
Yes, an external 24Vdc can be provided to the ATV320 drive in order to power up the display and program.  However, unlike many of the Altivar drives, you don't use the P24 terminal on the ATV320 for this purpose. The P24 terminal is dedicated to the STO terminals on the ATV320. Instead connect your external 24VDC to the +24 terminal and any of the COM terminals.

 