Issue:
Setup function block GearIn_LXM28 so that the master and slave drives follow each other perfectly

Product Line:
LXM28

Resolution:
The NUM of the GearIn_LXM28 function block should be set to 1280000 and the DENUM should be set to 8192 (2048 x 4).
This will make the perfect gear between the master and slave.