What's the difference between the 3 ATV312 LED's flashing and scrolling?

Issue
What's the difference between the 3 ATV312 LED's flashing and scrolling?

Product Line:
ALTIVAR 312

Environment:
All 

Cause:
Installation / Setup

Resolution:
Lights flashing on the ATV312 display means that the drive is currently in partial local control or fully in local control.
This is normally where one would hit mode and hold it for 3 seconds to go into these modes.
Scrolling LED's is where the drive is in Local mode rdy / run status.
Flashing LED's at the same time is where the drive is in Local mode programming mode.