What are the MCC Conversion and CONOMO accessories for Powerpact H, J, and L breakers?

Issue:
MCC Conversion Accessory

Product Line:
Circuit Breakers

Environment:
Powerpact H, J, L

Resolution:
The MCC Conversion Accessory (S429341 for H and J; S32606 for L) is added to the direct-mount rotary handle to add the following functions to the handle:
  • IP Degree of protection IP43, IK07. The IP is increased by a built-in gasket.
  • Door locking depending on device position.
    • The door cannot be opened if the circuit breaker is ON or in the tripped position. For exceptional situations, door locking can be temporarily disabled with a tool to open the door when the circuit breaker is closed. This operation is not possible if the handle is locked by a padlock.
    • Circuit-breaker closing is disabled if the door is open. This function can be deactivated.

Machine-tool control in compliance with CNOMO Control of a machine-tool is achieved by adding kit S32602 to the standard handle for L frame (S29342 for H, J frames is obsolete).
In addition to the standard functions, the kit offers the characteristics listed below:
  • Enhanced waterproofing and mechanical protection to IP54, IK08.
  • Compliance with CNOMO E03.81.501N. 