Technical FAQs

Ask a Question

Can a SDSA1175 be used on a 120 V, 1-phase, 2-wire application?

Issue:
SDSA1175 LED will not light illuminate when applied on a 120 V, 1-phase, 2-wire application?

Product Line:
Surge Protector

Environment:
SDSA1175

Cause:
single phase application

Resolution:
The SDSA1175 is configured to be used on a 120/240 V, 1-phase, 3-wire system. Applying this device on a 120 V 1-phase 2-wire application will not work properly because the indicating LED will not be functional. The SDSA1175 needs to have 240 V between both black leads in order to function properly. For 2-wire applications the correct device that should be used is the SDSA1175T.

*Note
Two SDSA1175 units may be installed to provide suppression on 208Y/120 Vac three-phase, four-wire services. Systems must be solidly grounded. Do not use the SDSA1175 on ungrounded systems.

Was this helpful?
What can we do to improve the information ?