Technical FAQs

Ask a Question

Video: How does the QO2DTI Manuel Transfer kit install on the QO breakers in a QO load center?

Issue:
Product Design Features

Product Line:
QO Circuit breakers and Load Centers

Environment:
QO Breaker accessories 

Resolution:
The QO2DTI Manuel transfer kit contains (1) Handle Interlock, (1) Utility Supply ID Label, (1) Generator Supply ID Label and instructions.
The QO2DTI is ONLY for use with Single Handle QO/QOB branch circuit breakers

This video is ONLY to supplement the INSTRUCTIONS that come with the kit. PLEASE Make sure to read the instructions and ALL the below SAFETY information that is located in the instructions BEFORE working on any electrical equipment.
A pdf copy of the complete instructions is attached below the video.

Make sure to turn OFF ALL Power supplying the equipment and verify the power is OFF using a properly rated voltage sensing device, BEFORE working on or with electrical equipment. 
Once all Safety steps are followed, begin the kit installation by following the instructions.
NOTE: Mount the circuit breaker side-by-side. Right-hand circuit breaker can be 2- or 3-pole. Left-hand circuit breaker can be 1- or 2-pole. To lock either circuit breaker handle in the ON(I) or OFF(O) position, order the attachment HLO1.
1) Place attachment on right-hand circuit breaker.

2) Hook tab (A) in slot at OFF(O) end. See figure on page 2 of instructions. 
3) Use a screw driver to bend tab (B) into slot at ON(I) end. See figure on page 2 of instructions  
4) Attach the labels to identify circuit breakers.

NOTE: BEFORE WATCHING THE VIDEO, PLEASE READ ALL INSTRUCTIONS AND SAFETY INFORMATION THAT COME WITH THE KIT AND NEVER WORK ON ENERGIZED EQUIPMENT.

REPLACE THE BELOW VIDEO WITH THE NEW VIDEO
Was this helpful?
What can we do to improve the information ?