What are the wire sizes for the main lugs of a HCP14508 panel?

Issue;
What size wires are accepted for the main lugs for HCP14508?

Product Line;
I line panelboard

Environment;
HCP I line panelboard 

Cause;
Main lug wire size

Resolution;
The lug is rated for 3 - 3/0 to 500 kcmil per phase al/cu due to NEC wire bending space rules. 
 