Video: How to set an ATV61/71 drive for feedback (analog output) to show motor frequency?

Issue:
How to set an ATV61/71 drive for feedback to show motor frequency?

Product Line:
Altivar 61, Altivar 71

Environment:
All models

Cause:
Feedback delivery from drive

Resolution:
Go to Menu 1 [Drive Menu] and then to 1.5 [Inputs/Outputs CFG].
Go to AO1 Configuration.
Set AO1 Assignment to motor freq.
Set analog output type to desired value (Voltage or Current).  
Set AO1  min Output and AO1 max Output as needed.  Typical options include 0-10VDC, 0-20mA, or 4-20mA.
Go to Menu 1.1 [Simply Start] or Menu 1.4 [Motor Control]
Set Max Frequency and set to 60 Hz to scale the analog output between 0 and 60 Hz.
Set Max Frequency to 50 Hz to scale the analog output between 0 and 50 Hz.

 