What is the ambient temperature operating range of the ATV12 series drives?

Issue:
What is the ambient temperature operating range of the ATV12 series drives?

Product Line:
ATV12 series drives.

Environment:
All models, All serial numbers.

Cause:
N/A

Resolution:

Ambient Air Temperature**

ATV12H018F1, ATV12H037F1
ATV12H018M2...H075M2
ATV12H018M3...H075M3
ATV12P models
Operation -10C to +40C without derating.  Up to +60C with derating.  Remove the blanking cover and de-rate at 2% per degree above 40C. 

ATV12H075F1
ATV12HU15M2, HU22M2
ATV12HU15M3...HU40M3
Operation -10C to +50C without derating.  Up to +60C with derating.  Remove the blanking cover and de-rate at 2% per degree above 50C. 

Storage temperature for all units is -25C to +70C

** UL ratings are up to 40C only.  Higher temperature ratings listed above are for non-UL listed applications only.