Technical FAQs

Ask a Question

How do I program and wire an ATV212 to run using 3-wire control?

Issue:
How do I program and wire an ATV212 to run using 3-wire control?

Product Line:
Altivar 212

Environment:
All

Cause:
Need to use 3-wire (momentary) control 

Resolution:

Programming:
Press MODE key to go into AUF
Arrow down to F---, and  press ENT key
Set F111 to 2
Set F112 to 49

Wiring:
Wire F terminal for forward Normally Open (NO), momentary close to Start
Wire R terminal for Normally Closed (NC) Stop 
 
Was this helpful?
What can we do to improve the information ?