How can two Altivar drives be controlled with one potentiometer?

Issue:
How can two Altivar drives be controlled with one potentiometer?

Product Line:
Altivar drives

Environment:
All

Cause:
N/A

Resolution:
Yes, one potentiometer is capable of serving as the speed reference for both drives.
Both Drives have to have Com jumpered 
Pot Wiper terminal goes to both AI1 inputs on Drive 1 and 2.
Pot com terminal goes to com on the drive 1 and 2 which com is jumpered.
Pot wires to Drive 1 +10vdc signal. 