Will a MH36800 fit in a HCP panel?

Issue:
Breaker for I-Line panel

Product Line:
Panelboards

Environment:
I-Line HCP

Cause:
Mounting

Resolution:
Neither the MA or MH breakers will fit in the wide side of this I-Line panel. The cam foot has no where to engage the back panel. Use the HCRU or older HCW interior instead.