Can the NQ Column Width panel be inverted to top or bottom feed in the field?
Issue:
With a NQ Column Width panel can you field change from bottom to top feed ?
Product Line:
NQ Panelboards
Environment:
Installation
Cause:
Re-entry from top ,,or bottom
Resolution:
The Column Width panel can be inverted in the field from bottom to top feed. The only issue is with a Main breaker originally lugged for Bottom feed (Lugs on OFF Side).
The Main does not have the option to move the lugs from the OFF side to the ON side for Top feeding . A new QBM32225TN Main breaker will have to be ordered for ON side Lugs,
which will allow for Top incoming feeding to Panel.
With a NQ Column Width panel can you field change from bottom to top feed ?
Product Line:
NQ Panelboards
Environment:
Installation
Cause:
Re-entry from top ,,or bottom
Resolution:
The Column Width panel can be inverted in the field from bottom to top feed. The only issue is with a Main breaker originally lugged for Bottom feed (Lugs on OFF Side).
The Main does not have the option to move the lugs from the OFF side to the ON side for Top feeding . A new QBM32225TN Main breaker will have to be ordered for ON side Lugs,
which will allow for Top incoming feeding to Panel.
Released for:Schneider Electric USA