Can you daisy-chain ZSI outputs for Powerpact H, J, L breakers with Powerpact P and R on the same level?

Issue:
Can you daisy chain Argos and Proxima trip units together for ZSI?

Product Line:
Circuit breakers

Environment:
Powerpact H, J, L, P, R

Resolution:
Yes, the ZSI outputs of these breakers can be linked together for bringing a common cable to a ZSI Interface Module, RIM, or upstream Powerpact/Masterpact breaker.
 