Can the logic be inversed on a logic input assigned as an external fault on the ATV61 and ATV71 drives?

Issue:
Can the logic be inversed on a logic input assigned as an external fault on the ATV61 and ATV71 drives?

Product Line:
ATV61/71

Environment:
All models

Cause:
N/A

Resolution:
Yes.  After setting an External Fault assignment to a logic input, the External fault config (LEt) determines the IO logic. 
If LEt = Active high, then the fault is triggered as the LI transitions from low to high.
If LEt = Active low, then the fault is triggered as the LI transitions from high to low.