What is the largest ampere size breaker that can be added to a HCP panel ?

Issue:
Largest amp size breaker in HCP panel.

Product Line:
Panelboards

Environment:
I-Line

Cause:
Selection of maxium size breaker
 
Resolution:
For the HCP the largest branch or main is an 800a due to wire bending space.