Why can I not see the Ethernet web page on and ATV61 or ATV71 drives?

Issue:
Why can I not see the Ethernet web page on and ATV61 or ATV71 drives?.

Product Line:
Altivar 61 and 71 drives

Environment:
All models and serial numbers with Ethernet IP option card VW3A3316

Cause:
Java 1.8 is not supported or webserver services are not enabled.

Resolution:
First, verify that webserver services are enabled via the "SERVICES" parameter:
From the main menu, navigate to the DRIVE menu -> [COMMUNICATION] -> [ETHIP] -> [SERVICES] and verify that Webserver services are not disabled.  

Next, check your computer's Java version and if 1.8 or later is installed, roll back the Java version to 1.7.67  See the document attached.  