Is it acceptable for NQ Panelboards to be applied on 400 Hz systems?

Issue:
Are NQ panelboards suitable for use on a 400 Hz system?

Product Line:
Panelboards

Environment:
NQ panelboards

Resolution:
Yes, NQ panelboards are approved for use at 400 Hz. However, the circuit breakers must be derated for 400 Hz applications.  See Data Bulletin https://www.schneider-electric.us/en/download/document/0100DB0101.