What is the color code for the red and green wires on a Powerpact M P R frame and Masterpact shunt trip or UVR?

Issue:
Color code for wire harness on shunt trip and UVR

Product Line:
Circuit Breakers

Environment:
Masterpact and Powerpact

Resolution:
The red wire is common (DC negative) and connects to terminal C1 or D1.
The green wire is the hot switched wire and connects to terminal C2 or D2.
A third wire is present on a communicating shunt trip and must be connected to terminal C3 and must be kept connected to the C2 source continuously.