Are the Powerpact two-device solution breakers with M38X suffixes UL listed?

Issue:
Are the Powerpact two-device solution breakers with M38X suffixes UL listed?

Product Line:
Circuit breakers

Environment:
Powerpact MCP

Resolution:
Even though Powerpact motor circuit protectors with suffix M38 have thermal and short-circuit protection, they are not UL 489 listed.
They are listed per UL 60947-4-1A and CSA C22.2 NO 60947-4-1-07.  See attached certificate and attached faceplate label.


1 Two-device solutions (these electronic motor protector circuit breakers include short circuit and overload protection)
—1 electronic motor circuit protector with a Micrologic 2.2 M electronic trip unit, plus
—1 contactor
2 The standard trip unit offers Class 5, 10 and 20 and phase unbalance or phase loss protection.