Technical FAQs

Ask a Question

How do I add a password on an ATV312?

How do I add a password on an ATV312?

Product Line:
ATV312, Altivar 312


Prevent program changes

You can add a password by setting parameter COd (PIN code 1).  This parameter is under the SUP menu (Monitoring).  Change from Off to to On and then change the display to a 4 digit code and push the Enter button.

To unlock the drive, go under the COd parameter again and enter the pin code saved. 

To reactivate the same pin code, change COd back to On and push the enter button. 

To change the pin code, once unlocked, change the pin code to another 4 digit code and pus enter to save. 

To disable the pin code, change the display to Off and then push Enter to save.

Was this helpful?
What can we do to improve the information ?