Are the 8903L, 8903LX, and 8903S Square D lighting contactors rated for LED lighting applications?

Issue:
Does Schneider Electric have documentation on LED ratings for the 8903L or 8903LX 30A rated lighting contactors?

Product Line: 
Full Voltage Lighting Contactors NEMA style,

Environment:
8903 line of NEMA Contactors

Cause:
Installation restrictions

Resolution:

As of 2017 Schneider Electric has tested the Class 8903 Type L/LX and Type S NEMA lighting contactors per NEMA-410-2015 and UL508: Table 46.1 and Section 61C test procedures for LED Loads.  This test specifies procedures up to 16A loads at 120VAC. Our testing was accomplished at 20A, 120VAC and conforms to all test requirements.
Schneider Electric's NEMA lighting contactors, Class 8903, are LED Ready.