Video: How can you program the ATV212 drive to run in local mode (face of the drive)?

Issue:
How can you program the ATV212 drive to run from in local mode (face of the drive)?

Product Line:
Altivar ATV21 and ATV212

Environment:
All

Cause:
Needs to use the run/ stop buttons on the face of the drive.

Resolution:
Programming as follows:
Push Mode until you see AUF
Once at AUF, arrow down to CNOD and set to 1 ( local mode) then press enter
Arrow up to FNOD, and set to 3 ( local knob for speed)

See that attached programming manual and video for assistance on setting up the reset of the drives programming settings.
 