GS1 and GS2 lug information

Issue:
Which GS fusible disconnect switches come with lugs?

Product Line:
GS1 and GS2

Environment:
US Product

Cause:
Some units come with lugs, and some units do not.

Resolution:
The following units come with lugs built in - these lugs are not replaceable (wire sizes are also specified):

GS1DDU3  -  AWG  #14 - #10
GS1DU3  -  AWG  #14 - #10
GS2EEU3  - AWG  #14 - #10
GS2EU3N  - AWG  #14 - #6
GS2GU3N  - AWG  #10 - #6
GS2JU3N  - AWG  #12 - #1

The 200 amp and above can have lugs added in the field: 
 

Terminal Lugs

For Use On:

Rating

No. of Wires per Lug

No. of Lugs per Terminal

Lug Size (AWG)

Wire Type

Lugs per Kit

Lug Kit 
Catalog Number

LK4DU3CN

30

1

1

#12–2/0

Cu

Standard

LK4GU3CN

60

1

1

#12–2/0

Cu

Standard

LK4JU3N

100

1

1

6–300 kcmil

Cu/Al

6

GS1AW403

LK4MU3N

200

1

1

6–300 kcmil

Cu/Al

6

GS1AW403

LK4QU3N

400

2

1

350 MCM—6

Cu/Al

6

GS1AW603

1

1

600 MCM—4

Cu/Al

6

GS1AW606

2

250 MCM—1/0

LK4SU3N

600

2

1

2 x 2–600 kcmil

Cu/Al

6

GS1AW503

LK4TU3N

800

2

2

2 x 2–600 kcmil

Cu/Al

12

GS1AW903

LK4UU3N

1000

2

2

2 x 2–600 kcmil

Cu/Al

12

GS1AW903

LK4WU3N

1200

2

2

2 x 2–600 kcmil

Cu/Al

12

GS1AW903

GS1DDU3

30

1

1

#14–#10

Cu

Standard

GS1DU3

30

1

1

#14–#10

Cu

Standard

GS2EEU3

30

1

1

#14–#10

Cu

Standard

GS2EU3N

30

1

1

#14–#6

Cu

Standard

GS2GU3N

60

1

1

#10–#6

Cu

Standard

GS2JU3N

100

1

1

#12–#1

Cu

Standard

GS2MU3N

200

1

1

6–300 kcmil

Cu/Al

6

GS1AW403

GS2QU3N

400

2

1

350 MCM—6

Cu/Al

6

GS1AW603

1

1

600 MCM—4

Cu/Al

6

GS1AW606

2

250 MCM—1/0

GS2SU3

600

2

1

2 x 2–600 kcmil

Cu/Al

6

GS1AW503

GS2TU3

800

2

1

2 x 2–600 kcmil

Cu/Al

6

GS1AW503