Can you get a pulse output on a variable speed drive?

Issue:
Can you get a pulse output on a variable speed drive?

Product Line:
Altivar 340
ATV340

Environment:
All

Cause:
Pulse output needed for signal sent back to PLC

Resolutuon:
The new ATV340 product has a PTO (Pulse Train Ouput available on connector CN4.
It is a  5Vdc differential RS422 signal with the output frequency per signal greater than or equal to 500 kHz.

 