Do the ATV61 and ATV71 drives have a built in ON delay timer for the logic inputs?

Issue:
Do the ATV61 and ATV71 drives have a built in ON delay timer for the logic inputs?

Product line:
Altivar 61 & 71

Environment:
All models, all serial numbers.

Cause:
Customer needs to delay the run command after LI1 closes. 

Resolution:
Under Menu 1.5 Inputs Outputs Config, go to LI1 Configuration and select LI1  On Delay. 
The default setting for this parameter is 0 ms, but can be set to 0 to 200ms. 

The time delay function is available on all the logic inputs.