What is the wire range/terminal lug data for General Duty fused and nonfused Safety Switch

Issue:
Product design features

Product Line:
General Duty Safety Switches

Environment:
Terminal Lug data

Cause:
Verification

Resolution:
Below is a table for the Terminal lug data for ALL the Square D General Duty Safety Switches. The below information is also located on each switch wiring diagram
 

Amperes

 Conductor per phase

Wire range per NEC Table 312.6 AWG / KCMIL

     Lug Wire Range
        AWG / KCMIL

30

1

12-6 Al or 14-6 Cu

12-6 Al or 14-6 Cu

60

1

12-3 Al or 14-3 Cu

12-2 Al or 14-2 Cu

100

1

12-1 Al or 14-1 Cu

12-1/0 Al or 14-1/0 Cu

200

1

6-250 Al/Cu

6-300 Al/Cu

400  NEMA 1

1  or
2

(1) 1/0 -600 Al/Cu or
(2) 1/0 – 300 Al/Cu

(1) 1/0 -750 Al/Cu or
(2) 1/0 -300 Al/Cu

400 NEMA 3R

2

1/0 – 250 Al/Cu

(1) 1-600 Al/Cu  or
(2) 1/0-250 Al/Cu

600

2

4-500 Al/Cu

4-600 Al/Cu

800

3

3/0 – 500 Al/Cu

3/0 – 500 Al/Cu