Will an EDBPA / EDBPAF handle lock kit, work with a Series E1 EDB , NF panelboard breaker?

Issue:
Will an  EDBPA / EDBPAF handle lock kit work with a Series E1 EDB breaker?

Product Line:
NF Panelboard

Environment:
Accessories for Branch breakers

Cause:
Series E1 breakers will not accept current Series E2 and E3 EDB Breaker handle lock accessories

Resolution:
Due to the Series E1 breaker NOT having a slot in the upper portion of the breaker , the currently available Series E2, E3, EDPA and EDPAF handle lock kits will NOT work .
Replace breakers with either Series E2 , or E3 breakers if accessory needed . See picture showing SLOT in the new Serie(s) Breakers below.










 