What is the terminal lug data for a 1200amp I Line main breaker panel?

Issue:
Lug cable size

Product Line:
Panelboard

Environment:
I-Line

Cause:
Installation

Resolution:
Powerpact P or R breaker Lug wire Range = (4) 3/0-500kcmil Al/Cu per phase and Neutral.
Wire Bending space per NEC Table 373-6 = (4) 3/0-500kcmil Al/Cu per phase and Neutral
 