What is the tripping current for a Multi 9 GFP Ground Fault Protector?

Issue:
What is the tripping current for a Multi 9 GFP Ground Fault Protector?

Product Line:
Circuit breakers

Environment:

Multi 9 C60 Ground Fault Protectors

Resolution:
Tripping currents are as follows:
GFP30     Must trip at 29.9 mA; must not trip below 22.1 mA      
GFP100     Must trip at 98.9 mA; must not trip below 73.1 mA      
GFP300     Must trip at 299 mA; must not trip below 221 mA      
 