PowerChute Business Edition does not install successfully on Red Hat Enterprise Linux 7.x and Oracle Linux 7.x

Issue:
PowerChute Business Edition (PowerChute) does not install, the following error message is displayed:
       ./config.sh:line 130: /bin/java/jre/<jre version>/bin/java: Not a directory

Product Line:
PowerChute Business Edition

Environment:
OS: Red Hat Enterprise Linux (RHEL) 7.x x64, and 
Oracle Linux 7.x x64
Build: PowerChute Business Edition 9.1.0, 9.1.1, 9.2, 9.0.1, 9.0.2, 9.0.3 OEM Basic and 25 Node Deluxe

Cause:
OpenJDK is installed in the directory used by PowerChute for the bundled private Java Runtime Environment (JRE).

Resolution:

This issue has been resolved in PowerChute Business Edition version 9.2.1 and 9.0.4 availabe at this link https://www.schneider-electric.us/en/faqs/FA304446/

Note:  Though an error message is displayed, a PowerChute directory is created that is used to resolve the issue in Step 4.

1 - Install standalone x86 Java JRE. The RPM Package Manager installs the JRE in the /usr/java/ directory.

     Note: We recommend installing the version of the Java JRE that was originally packaged with PowerChute:  
            9.2.0/9.0.3       JRE jre1.8u31

            9.1.1/9.0.3       JRE jre1.7u25
            9.1.0/9.0.2       JRE jre1.6u37
            9.0.0/9.0.1       JRE jre1.6u19 


2 -  Download the JRE Config Tool to change the location of the Java JRE used by PowerChute to the  JRE version installed in step 1:
    
  http://www.apc.com/tools/download/software_comp.cfm?sw_sku=SFPCBEJRE&id=125&swfam=125

3 - Run the JRE Config Tool.
     When prompted, enter the new system JRE directory e.g. (/usr/java/jre1.7.0_25) and answer Yes to all prompts in order to change the JRE used by PowerChute.

4 –
For all versions mentioned above navigate to the PowerChute directory and edit the config.sh script file to use the new Java JRE as follows:
  •      cd /opt/APC/PowerChuteBusinessEdition/Agent
  •      Edit config.sh and change the location of the Java JRE directory:
              e.g.
             /bin/java/jre/1.7.0_25/bin/java -jar ./lib/pcbeconfig.jar $1 $2 $3 $4 $5
             to
            /usr/java/jre1.7.0_25/bin/java -jar ./lib/pcbeconfig.jar $1 $2 $3 $4 $5


5 – For versions 9.0.1, 9.0.2 and 9.0.3 edit config.sh script file also to make the following additional update. Change:
 
/bin/java/jre/1.7.0_25/bin/java -classpath ./lib/m11.jar:./lib/pcbe_ds.jar:./lib/dom4j-1.5.jar:./lib/jaxen-1.1.4.jar:./comp/MicroLinkPowerSource.jar:./lib/MakeUsageDescriptorMap.jar com.apcc.MakeUsageDescriptorMap.MakeUsageDescriptorMap ./m11.cfg ./lib/ulDictMaster.xml 1>/dev/null
 
to
 
/usr/java/jre1.7.0_25/bin/java -classpath ./lib/m11.jar:./lib/pcbe_ds.jar:./lib/dom4j-1.5.jar:./lib/jaxen-1.1.4.jar:./comp/MicroLinkPowerSource.jar:./lib/MakeUsageDescriptorMap.jar com.apcc.MakeUsageDescriptorMap.MakeUsageDescriptorMap ./m11.cfg ./lib/ulDictMaster.xml 1>/dev/null
 
6 - Run the configuration file
     ./config.sh


7 - PowerChute should be communicating with the UPS and should be fully configurable. Launch PowerChute in the web browser to verify.
 