What can cause an error code EPHO on the ATV21 and ATV212 drives?

Issue:
ATV212: EPHO or output phase loss fault

Product Line:
ATV212, ATV21

Environment:
All models and serial numbers

Cause:
Motor may not be connected.

Resolution:
Check that the motor is connected to the drive. If the unit has a bypass option you will have to disable the output phase loss protection by setting F605 to 0.