Are there any branch breaker restrictions in a 400a Nema 3R NF panel ?

Issue:
What are the branch breaker restrictions for NF 400A N3R panels?

Product Line:
Panelboards

Environment:
NF

Cause:
Selection

Resolution:
The largest true branch is 125a and sub-feed breaker is 150a . Also 5 branches at 70a or more is a limit .