Are the Powerpact H, J, and L Frame breaker with Field-Interchangeable Trip Units available in fully rated or 100% rated?

Issue:
100% rating for Powerpact H J L with interchangeable trip units

Product Lines:
Circuit Breakers

Environment:
Powerpact H J L Breakers

Resolution:

Yes, the catalog number for the 80% rated breaker has “T” in the 9th character space. 
The catalog number for a 100% rated breaker uses “R” in the 9th character place.  For example, HDL36015T or HDL36015R or LGL36400TU31X or LGL36400RU31X).
100% rated H- and J-frame circuit breakers have copper lugs and can only be used with copper wire.