Why does a ZBVG3 show some illumination at 12vac ? This 120v rated

Published date: 19 September 2019

Issue:
Strange illumination

Product Line:
Push Buttons

Environment:
22mm ZB4 and ZB5

Cause:
LED Pilot light modules

Resolution:
Due to the design of LED lamps, they will illuminate at lower voltages. Consider using a bleeder resistor across the terminals to elimate that problem or use a different style pilot light.