Where can I find instructions for ATV12 drive basic programming?

Issue:
Where can I find instructions for ATV12 drive basic programming?

Product line:
Altivar 12

Environment:
All models, all serial numbers
 
Cause:
Basic Programming for the ATV12 drive
 
Resolution:
Enter and scroll down to CONF.
Enter and scroll down to FULL.

DRC Menu: 
(Set using motor's nameplate data)
BFR Standard Motor frequency (usually 60Hz)
UNS Rated Motor Voltage
FRS Rated Motor Frequency (usually 60Hz)
NCR Rated Motor Current (motor's FLA)
NSP Rated Motor Speed (in rpm's)
TFR Max Frequency (usually 60Hz)
CTT Motor control type

FUN Menu:
ACC Acceleration
DEC Deceleration
LSP Low Speed (0-60Hz)
HSP High Speed 
ITH Motor Thermal (match FLA)
UFR Voltage boost
CLI Current limitation (FLA multiplied by SF)
RRS Reverse assign

I-0 Menu:
TCC 2/3 wire type (2C or 3C)
TCT 2 wire type control (LEL, trn, PFO)



Refer to the ATV12 Programming manual BBV28581.  https://www.schneider-electric.us/en/download/document/BBV28581/