Technical FAQs

Ask a Question

Can the ATV600 and ATV900 Process Drive run multiple motors ?

Issuse:
Can the ATV600 and ATV900 Process Drive run multiple motors?

Product Line:
ATV600 ATV900 Altivar Process Drive

Environment:
All

Cause:
To simplify application

Resolution:
Yes, you can run multiple motors on a single drive.  Each motor will need seperate external overload protections.
Both motors will share the same operations,  the start/stop and speed reference controls.  
The heavy duty version of the drive should be sized according to the sum of both the horsepower and full load amps of both motors.
Was this helpful?
What can we do to improve the information ?