Video: What are the installation tools for QOB-VH (110, 125, 150 A) Bolt-on Circuit Breaker?

Issue:
What are the installation tools for QOB-VH (110, 125, 150 A) Bolt-on Circuit Breaker?

Product Line:
QOB-VH (110, 125, 150 A) Bolt-on Circuit Breaker
QOB2150VH
QOB3110VH
QOB3125VH
QOB3150VH

Environment:
Installation into panel, installation of cables

Cause:
48940-072-03 Instructions do not state tools required

Resolution:
The bolt-on screw uses a 1/8 inch hex (allen wrench).
The wire binding screw in the lug uses a  3/8 inch hex (allen wrench).
For torque requirements see breaker label and/or breaker instruction sheet below:
Link to instructions 48940-072-03.

The following video demonstrates how to install 110-150A QOB VH breakers: