What is the minimum distance between Modbus Plus taps?

For the Modbus Plus taps the minimum distance between nodes is ten feet, 10ft. The length of the drop from the tap is included, the formula is (one drop length + second drop length + distance between taps) must be greater than 10 feet. If the drops are long enough there is no minimum distance between taps.